MI 3108 EurotestPV

Photovoltaic and electrical installation testers

MI 3108 EurotestPV is a combined photovoltaic tester and electrical installations safety tester. It enables complete testing of electrical installations according to EN 61557 standards and in addition performs all necessary tests required on single-phase photovoltaic (PV) installations. This includes all of the tests as required by EN 62446, but also includes I - U characteristic, Calculation of STC values as required by EN 61829 and power measurements on Inverter’s DC and AC sides. The unit is designed for the demanding working conditions (up to 1000 V, with 15 A DC). To greatly improve user safety the MI 3108 EurotestPV comes with the PV Safety Probe which ensures safe disconnection every time.

Sets

Standards applied

Building LV Installation

  • EISinsp Competences: Low Voltage Electrical Installation Safety Inspection
  • EISc Competences: Low Voltage Electrical Installation Safety for Contractors and Maintainers
  • IEC/EN 60364 Electrical Installations for Buildings series
  • IEC/EN 60364-4-41 Electrical Installations for Buildings - Protection against electric shock
  • IEC/EN 61008-1 Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs)
  • IEC/EN 61557 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - series
  • IEC/EN 61557-1 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 1: General requirements
  • IEC/EN 61557-2 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 2: Insulation resistance
  • IEC/EN 61557-3 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 3: Loop impedance
  • IEC/EN 61557-6 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 6: Effectiveness of residual current devices (RCD) in TT, TN and IT systems
  • IEC/EN 61557-7 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 7: Phase sequence
  • IEC/EN 61557-10 Electrical safety in low voltage distribution systems up to 1 000 v a.c. and 1 500 v d.c. - Equipment for testing, measuring or monitoring of protective measures - Part 10: Combined measuring equipment for testing, measuring and monitoring of protective measures
  • BS 7671 IEE Wiring Regulations (18th edition)

Earthing and lightning protection 

  • LPSinsp Competences: Lightning Protection of Buildings Inspection
  • LPSc Competences: Lightning Protection of Buildings for Contractors and Maintainers
  • IEC 62305 Protection against lightning - series
  • IEC/EN 61557-5 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 5: Resistance to earth
  • IEC/EN 61557-4 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 4: Resistance of earth connection and equipotential bonding

Photovoltaic systems

  • PVV Competences: Photo Voltaic Installations Safety/Quality
  • IEC / HD 60364-7-712 Low Voltage Electrical Installation Safety - Special installtions and locations
  • IEC/EN 62446 Photovoltaic (PV) systems - Requirements for testing, documentation and maintenance
  • IEC/EN 61829 Crystalline silicon photovoltaic (PV) array – On-site measurement of I / V characteristics

Power quality 

  • PQA Competences: Power Quality Analyzing & Reporting
  • IEC/EN 61557-12 Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 12: Power metering and monitoring devices (PMD)

Instrument safety towards user

  • IEC/EN 61010 Safety requirements for electrical equipment for measurement, control, and laboratory use - series
  • IEC/EN 61010-1 Safety requirements for electrical equipment for measurement, control, and laboratory use - Part 1: General requirements

EMC safety

  • IEC/EN 61326 Electrical equipment for measurement, control and laboratory use - EMC requirements - series
  • IEC/EN 61326-1 Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 1: General requirements

Properties

Measuring functions

Photovoltaic installations:

  • Measurements on DC side of PV installation:
  • Voltage, current, power;
  • Uoc (Open Circuit Voltage) and Isc (Short Circuit Current);
  • I - U curve of PV modules and strings;
  • Irradiance;
  • Module temperature.
  • Measurements on AC side of PV installation:
  • Voltage, current, power;
  • Efficiency of PV module, inverter, PV system calculation.

Electrical installations:

  • Insulation resistance;
  • Continuity of PE conductors;
  • Line impedance;
  • Loop impedance (sub-functions with high current and without RCD tripping);
  • RCD testing (type AC, A and B);
  • Earth resistance;
  • AC current (load and leakage);
  • TRMS voltage, frequency, phase sequence;
  • Power, energy, harmonics.

Key features

Photovoltaic installations:

  • Calculation of STC values: the measured current and voltage values are, according to environment conditions, recalculated to Standard Test Condition values which makes possible, to compare the results even if they were taken under different test conditions.
  • Graphical representation: the I-V characteristic of PV module or string is graphically represented on LCD display.
  • Power and efficiency measurements: 2 voltage & 2 current channels for simultaneous AC & DC parameters measurements.
  • PV Remote Unit: Optional unit for simultaneous measurements of solar irradiation and temperature of PV module.

Electrical installations:

  • RCD Auto: Automated RCD testing procedure significantly reduces test time.
  • Trip Lock function: Loop impedance test are performed without tripping the RCD.
  • B type RCD testing: is supported.
  • Earth resistance measurement: instrument supports 3-wire earth resistance testing.
  • Built-in fuse tables: for automatic evaluation of the line / loop impedance results.
  • Online voltage monitoring: monitors all 3 voltages in real time.
  • Scope function: real-time U/I scope.
  • Harmonics analysis: 1-phase power and energy measurements with up to 11th harmonics analysis is supported.
  • Memory: Up to 1800 test results or up to 500 graphical results with timestamp can be stored in internal memory.
  • BT connectivity: it enables BT communication with Android tablets and smart phones via optional BT dongle.
  • Android application: enables advanced data management APP EuroLink PV and EuroLink Android.
  • PC SW EuroLink PRO enables downloading, uploading, review, analyses and printing of test results.

Technical data

  • Dimensions (w x h x l): 230 x 103 x 115 mm
  • Mass (without accessories): 1.3 kg

Applications

Special locations 

  • Low voltage photovoltaic installations

Specifications

Downloads

Download File Language Version Release Notes Type Size View Download
Datasheet MI 3108 EurotestPV en 2017 18.11.2017 pdf 943.05 KB
Datasheet PC SW EuroLink PRO en 1.0 13.03.2014 pdf 915.07 KB
Manual A 1378 PV Remote Unit en 2.3 04.04.2019 20 752 010 pdf 834.2 KB Login
Manual MI 3108 EurotestPV en 1.10.2 03.07.2019 20 751 987 pdf 3.72 MB Login
PC Software Photon Module DB en 2016 13.02.2017 Readme xls 13.14 MB Login
PC Software SW 0101 EuroLink PRO (EU) en 4.36 20.12.2018 Readme zip 61.24 MB Login
Android SW 1307 Eurolink Android en 04.01.2021 Google Play jpg 40.26 KB
Firmware Firmware A 1378 en 2.09 28.08.2019 zip 345.49 KB Login
Firmware Firmware MI 3108 en 2.52 25.02.2020 zip 2.22 MB Login